Specifications
Highlight:
COP:
4.1
Compressor:
Panasonic On-Off Compressor
Refrigerant:
R32
Condenser:
High-Efficiency Tank Heat Exchanger.
Fan Motor:
AC
Circulation Pump:
Optional Built-in On-Off Water Pump
Control:
WIFI +APP +4.3/5 Inch Touch Screen Panel
Function:
Hot Water+Room Heating
COP:
4.1
Compressor:
Panasonic On-Off Compressor
Refrigerant:
R32
Condenser:
High-Efficiency Tank Heat Exchanger.
Fan Motor:
AC
Circulation Pump:
Optional Built-in On-Off Water Pump
Control:
WIFI +APP +4.3/5 Inch Touch Screen Panel
Function:
Hot Water+Room Heating
Description
On-Off Air to Water Heat Pump-A2 (R32)

What is an air source heat pump? On-Off Air to Water Heat Pump-A2 (R32) 0


  • An air source heat pump (ASHP) is a heating and cooling system that extracts heat from the ambient air and transfers it indoors or outdoors, depending on the desired effect. 

It uses the principles of refrigeration to absorb heat from the outside air and deliver it inside a building for heating water tank and room purposes. 

During hot weather, the process can be reversed to provide cooling by extracting heat from inside and releasing it outside. 

ASHPs are known for their energy efficiency and can be used in residential, commercial and industrial settings. They are considered a renewable and environmentally-friendly alternative to traditional heating and cooling systems.


Features of the A2 Series Air-to-Water Heat Pump


  • On-Off Air to Water Heat Pump-A2 (R32) 1 High Efficiency:  The A2 series air-to-water heat pump uses a high-efficiency Panasonic compressor combined with the efficient heat exchangers for optimal performance.


  • Diverse functions: The A2 series air-to-water heat pump offers cooling, heating, and hot water supply, providing year-round comfort and efficiency forOn-Off Air to Water Heat Pump-A2 (R32) 2 various applications.



  • Easy installation: Optional integrated features include a built-in circulation pump, expansion tank, and backup electric heating within the heatOn-Off Air to Water Heat Pump-A2 (R32) 3 pump, making installation easier and more convenient.


  • Quiet: The A2 Series heat pump is designed with low noise operation, ensuring minimal sound disruption while providing efficient heating and cooling. Its advanced technology and optimized components help reduce noise levels, making it ideal for residential and commercial settings where quiet operation is essential.

On-Off Air to Water Heat Pump-A2 (R32) 4

  • Eco-Friendly: The A2 series heat pump uses R32 refrigerant, an environmentally friendly refrigerant with low global warming potential (GWP). R32On-Off Air to Water Heat Pump-A2 (R32) 5 offers improved energy efficiency, reduces carbon emissions, and provides a sustainable solution while maintaining optimal performance and reliability. This refrigerant helps meet eco-friendly standards and contributes to a greener environment.


Line-Up

Model 

A2-04

A2-05

A2-07

A2-10

A2-14

A2-18

Power supply 

V/HZ/Phase 

200-240/50/1




380-415/50/3

ERP rating 

/

A++

A++

A++

A++

A++

A++

Rated heating capacity (A7/W35)*

kW

4

5

7

10

14.4

18

Rated heating input power *

kW

0.98

1.23

1.72

2.46

3.54

4.42

COP *

W/W

4.08

4.08

4.08

4.06

4.07

4.07

Heating capacity (A-2/W35)**

kW

3.2

4

5.6

8.0

11.5

14.4

Heating input power **

kW

1.1

1.4

1.9

2.7

4.0

5.0

COP **

W/W

2.90

2.91

2.90

2.91

2.90

2.89

DHW heating capacity (A20/W15-55)

kW

5.0

6.0

8.0

12.0

15.8

20.0

Rated DHW power input 

kW

1.17

1.40

1.87

2.81

3.73

4.69

COP

W/W

4.28

4.28

4.28

4.27

4.25

4.26

Rated cooling capacity (A35/W7)

kW

2.88

3.6

5.04

7.8

10.4

13.0

Rated cooling power input 

kW

1.00

1.25

1.75

2.74

3.63

4.52

EER

W/W

2.88

2.88

2.88

2.85

2.86

2.87

Model 

A2-22

A2-27

A2-37

Power supply 

V/HZ/Phase 

380-415/50/3

ERP rating 

/

A++

A++

A++

Max heating capacity (with E-heating )

kW

31

36

46.1

Rated heating capacity (A7/W35)*

kW

22.1

27.2

37.1

Rated heating input power *

kW

5.46

6.68

9.16

COP *

W/W

4.05

4.07

4.05

Heating capacity (A-2/W35)**

kW

17.7

21.8

29.7

Heating input power **

kW

6.1

7.5

10.2

COP **

W/W

2.91

2.90

2.90

DHW heating capacity (A20/W15-55)

kW

24.0

32.0

42.0

Rated DHW power input 

kW

5.61

7.53

9.91

COP

W/W

4.28

4.25

4.24

Rated cooling capacity (A35/W7)

kW

16.0

21.0

27.5

Rated cooling power input 

kW

5.6

7.3

9.7

EER

W/W

2.85

2.87

2.84


Tags: